State number
Correction factor that removes the influence of pressure and temperature on the energy content of a gas volume.
A gas meter measures operating cubic metres – the volume under the conditions prevailing at the meter right now. Billing, however, uses the standard state: 0 °C and 1,013.25 mbar. The Zustandszahl translates between the two.
It depends mainly on two things: the geodetic altitude of the connection – the higher, the lower the air pressure – and the network's supply pressure. For household connections on the low-pressure network, typical values lie between 0.90 and 0.98; at altitude it drops noticeably. Where a connection is supplied at a higher billing pressure – medium pressure for commercial and industrial sites – z is greater than 1 instead: at 1 bar gauge pressure it is around 1.9, because the same operating cubic metre holds almost twice as much gas.
The effect of the z-number
- Volume
- 1,000 m³
- Calorific value
- 11.2 kWh/m³
- z = 0.98 (coast)
- 10,976 kWh
- z = 0.90 (highland)
- 10,080 kWh