Jump to Content

Capacity charge

A charge per kilowatt of capacity used, based on the highest quarter-hour peak measured during the year.

Updated: August 2026

Drawing a lot of power at once forces the grid operator to lay thicker cables and install larger transformers – regardless of how many hours a year that happens. So customers with load metering pay not only for energy but for capacity.

Grid fee = Capacity charge [€/kW·a] × Annual peak load [kW] + Unit rate [ct/kWh] × Consumption [kWh]

Who is affected#

The statutory criterion is consumption alone: from an annual consumption of 100,000 kWh, registering load metering (RLM) becomes mandatory (§ 12 StromNZV) – and then the actual load curve counts rather than a standard load profile. The law names no capacity threshold in kW. Some distribution grid operators do work with their own internal cut-offs – a connection capacity, say, above which they require load metering even below 100,000 kWh. Those live in the technical connection conditions or the price sheet, not in the regulation.

Two price sheets, two time bases#

Grid operators publish two price sheets for RLM customers, split by Benutzungsstunden (hours of use: annual consumption ÷ annual peak load): one for fewer than 2,500 hours a year with a low capacity charge and a high unit rate, and one from 2,500 hours upwards with the reverse ratio. Customers with an even load are better off on the second – and which one applies only becomes clear at year end from the metered values.

A single quarter hour decides it

Annual consumption
420,000 kWh
Highest quarter hour
180 kW
Capacity charge
€95/kW·a
Capacity component
€17,100
Saving from shaving 20 kW off the peak€1,900 a year

Related but not identical: reactive energy. It too is billed only to customers with load metering, and only above an agreed threshold.