Reactive energy
The share of electrical energy that does no useful work but builds up electric and magnetic fields – measured in kvarh and charged once it exceeds an agreed limit.
Motors, transformers and fluorescent lamps need magnetic fields to work. The energy for those oscillates back and forth between grid and device without being consumed – but it loads the lines all the same.
Active, reactive and apparent power
The beer glass model
Active power (kW) does the work; reactive power (kvar) builds the magnetic fields in motors and transformers. Together they load the grid as apparent power (kVA). Households pay nothing for reactive energy – commercial customers with load metering do, once they exceed an agreed limit.
When it is billed#
Household customers pay no reactive energy. For customers with registering load metering, however, the grid operator agrees a limit – usually a power factor cos φ of 0.9, which corresponds to reactive energy of around 50 % of the active energy. Exceed it and the excess reactive energy is billed in kvarh.
The reference quantities
- Active energy in the month
- 40,000 kWh
- Allowance at cos φ 0.9
- 19,400 kvarh
- Reactive energy metered
- 26,000 kvarh
- Billable
- 6,600 kvarh